H07RN-F 3G2.5 cut to length

Description

Description

Standards

  • Product
    EN 50525-2-21; HD 22.4; HD 516; IEC 60245-4 type 66; NF C32-102-4

Application

H07RN-F flexible cable is intended for installations with moving equipments, electric appliances and for building sites also for motors in lifting  appliances -machine tools, etc ... The cable may be rated up to 0,6/1 kV where the installation has built-in protection.

This range of cables is recommended in dry, damp or wet workshops, indoor and outdoor, for example in explosive atmosphere(as ATEX) according to regulation of the country and with some additional  recommendations and  also for industrial devices  and agricultures workshops ...

This cable can be used in refrigerating installations.

Installation

This cable can be installed in open air or be buried but with extra mechanical protection.

Conductors laid up 

Assembled conductors.

Nota

Max continuous operating conductor temperature in normal use :

+60°C   (in every case of mobile installation)

+85°C (in fixed and protected installation)

+200°C ( in short circuit )

 

Permissible current rating is measured for an ambient temperature of 30°C and a maximum operating and conductor temperature of 60°C . For other temperature please refer to correction factors .

European Directive  RoHS :  Compliant

SY+ :  French  directive for  lead free materials in materials.

Characteristics

Characteristics

Konštrukčné vlastnosti

Konštrukčné vlastnosti

Bez olova
Yes
Farba plášťa
Black
Flexibilita vodiča
Flexible class 5
Izolácia
Cross-linked synthetic elastomer type EI 4
Materiál vodiča
Bare annealed copper stranded
Tvar vodiča
Circular
Vonkajší plášť
Cross-linked synthetic elastomer type EM 2
With Green/Yellow core
Yes

Rozmerová charakteristika

Rozmerová charakteristika

Prierez vodiča
2,5 mm²
Počet žíl
3
Approximate weight
195 kg/km
Maximum outer diameter
14,0 mm
Minimum outer diameter
10,9 mm

Elektrická charakteristika

Elektrická charakteristika

Max. linear resistance, phase conductor
7,98 Ohm/km
Menovité napätie Uo/U
450/750 V
Permissible current rating in open air
32 A
Phase reactance 50 Hz - trefoil formation
- Ohm/km
Voltage drop, single phase
16,2 V/A.km

Mechanické vlatnosti

Mechanické vlatnosti

Rezistencia voči mechanickým útokom
Very good
Flexibilita kábla
Flexible

Užívateľské vlastnosti

Užívateľské vlastnosti

Balenie
Cut to length
Dĺžka
- m
Chemical resistance
Accidental
Odolnosť voči vode
Good
Oheň retardujúce káble
IEC 60332-1-2
Doporučená max. teplota vodiča
85 °C
Max. skratová teplota vodiča
200 °C
Minimum dynamic operating bending radius
84,0 mm
Minimum static operating bending radius
42 mm
Prevádzková teplota, rozpätie
-25 ... 55 °C
Rezistencia voči oleju
Yes
Rezistencia voči poveternostným podmienkam
Very good
RoHS compliant
Yes

Resources

Resources

Selling & delivery Information

Marking
USE <'HAR> H07RN-F N (x or G) S mm²
N = number of cores

G = with Green-Yellow
x = without Green-Yellow
S = section in mm²

Declaration of Performance

  • Declaration of Performance n� : 1000023-FRBH
  • Certification Date : 15. 3. 2022
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : NB 1812
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close