H07RN-F 3G70 cut to length

Popis

Popis

Normy

  • Product
    EN 50525-2-21; HD 22.4; HD 516; IEC 60245-4 type 66; NF C32-102-4

Application

H07RN-F flexible cable is intended for installations with moving equipments, electric appliances and for building sites also for motors in lifting  appliances -machine tools, etc ... The cable may be rated up to 0,6/1 kV where the installation has built-in protection.

This range of cables is recommended in dry, damp or wet workshops, indoor and outdoor, for example in explosive atmosphere(as ATEX) according to regulation of the country and with some additional  recommendations and  also for industrial devices  and agricultures workshops ...

This cable can be used in refrigerating installations.

Installation

This cable can be installed in open air or be buried but with extra mechanical protection.

Conductors laid up 

Assembled conductors.

Nota

Max continuous operating conductor temperature in normal use :

+60°C   (in every case of mobile installation)

+85°C (in fixed and protected installation)

+200°C ( in short circuit )

 

Permissible current rating is measured for an ambient temperature of 30°C and a maximum operating and conductor temperature of 60°C . For other temperature please refer to correction factors .

European Directive  RoHS :  Compliant

SY+ :  French  directive for  lead free materials in materials.

Charakteristika

Charakteristika

Konstrukční charakteristika

Konstrukční charakteristika

Bezolovnatý
Yes
Conductor flexibility
Flexible class 5
Conductor shape
Circular
Isolace
Cross-linked synthetic elastomer type EI 4
Material jádra
Bare annealed copper stranded
Outer sheath
Cross-linked synthetic elastomer type EM 2
Sheath colour
Black
With Green/Yellow core
Yes

Rozměrová charakteristika

Rozměrová charakteristika

Conductor cross-section
70 mm²
Počet jader
3
Approximate weight
3110 kg/km
Maximum outer diameter
48,3 mm
Minimum outer diameter
38,4 mm

Electrical characteristics

Electrical characteristics

Max. linear resistance, phase conductor
0,272 Ohm/km
Permissible current rating in open air
262 A
Phase reactance 50 Hz - trefoil formation
- Ohm/km
Rated Voltage Uo/U (Um)
450/750 V
Voltage drop, single phase
0,64 V/A.km

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Very good
Cable flexibility
Flexible

Charakteristika použití

Charakteristika použití

Packaging
Cut to length
Length
- m
Chemická odolnost
Accidental
Water proof
Good
Samozhášivost
IEC 60332-1-2
Max. conductor temperature in service
85 °C
Minimum dynamic operating bending radius
108,0 mm
Minimum static operating bending radius
54 mm
Oil resistance
Yes
Operating temperature, range
-25 ... 55 °C
RoHS compliant
Yes
Short-circuit max. conductor temperature
200 °C
Weather resistance
Very good

Zdroje

Zdroje

Prodejní informace & o dodávkách

Marking
USE <'HAR> H07RN-F N (x or G) S mm²
N = number of cores

G = with Green-Yellow
x = without Green-Yellow
S = section in mm²

Prohlášení o vlastnostech

  • Prohlášení o vlastnostech č. : 1000023-FRBH
  • Datum certifikace : 15.03.22
  • AVCP (posuzování a ověřování stálosti výkonu) : System 3
  • Oznámený subjekt : NB 1812
  • Deklarovaný výkon : Eca

Kontaktujte nás

Témata, o kterých si přejete získat více informací:

Požadovaná pole*

Zkontrolujte prosím svůj údaj a zkuste to znovu

E-mailová adresa musí obsahovat jediný znak @

Ochránce osobních údajů

Máte právo vznést námitku proti zpracování svých osobních údajů a/nebo jejich použití pro přímý marketing nebo komerční účely

Děkujeme vám!

Děkujeme, že jste nás kontaktovali. Brzy se s vámi spojíme.

Chyba

Došlo k chybě. Zkuste prosím aggain.

Zavřít